• 100% recyclable when returned to the manufacturer
• reduces heat loss/gain of air ducts
• made from recycled denim fabric diverted from landfill
• Cotton is a rapidly renewable resource
• Low Voc’s
• No irritants
• Use facilitates compliance of ASHRAE 90.1-1999
Quiet Natural Fiber Liner (Patent Pending) is a thermally bonded HVAC insulation that offers superior acoustic and thermal performance. Made from natural fibers, Quiet Liner contains no fiberglass and does not itch or cause skin irritation. The fibers used to manufacture Quiet Liner offer excellent sound absorption properties. The air stream surface of Quiet Liner is overlaid with a durable, fire-resistant black facing providing additional strength to the product. Both the insulation and the facing are treated with an EPA registered anti-microbial agent.
Quiet Natural Fiber Liner (Patent Pending) is a thermally bonded HVAC insulation that offers superior acoustic and thermal performance. Made from natural fibers, Quiet Liner contains no fiberglass and does not itch or cause skin irritation. The fibers used to manufacture Quiet Liner offer excellent sound absorption properties. The air stream surface of Quiet Liner is overlaid with a durable, fire-resistant black facing providing additional strength to the product. Both the insulation and the facing are treated with an EPA registered anti-microbial agent. USES:
Quiet Natural Fiber Liner is used primarily as an acoustical liner designed for HVAC sheet metal ducts to absorb unwanted noise from multiple sources. Quiet Liner also reduces heat gain or loss. Quiet Natural Fiber Liner contains no harmful irritants and is safe to handle and install.
Flame Spread Max: 25
Smoke Developed Max: 50
Class A / Class 1
ASTM E 84
UL 723
NFPA 255
Corrosion Resistance
Pass No Growth
ASTM G 21
ASTM C 1338
ASTM C 739
Bacteria Resistance
Pass No Growth
ASTM G 22
Water Vapor Absorption
Less Than 1% By Weight
ASTM C 1104
Product Compliance's
Quiet Natural Fiber Liner has the physical properties that
regularly meet the requirements of the following current specifications,
standards, and codes.
FIRE SAFETY STANDARDS
NFPA 90A Installation of Air Conditioning and Ventilating Systems
NFPA 90B Installation of Warm Air Heating and Air Conditioning System
BUILDING CODES
ICBO International Conference of Building Officials
BOCA Building Officials and Code Administrators
CABO Council of American Building Officials
SBCCI Southern Building Code Congress International
Thermal Performance
Tested in accordance with ASTM C518
PRODUCT
K-VALUE
C-VALUE
R-VALUE
Thickness
Inch
(mm)
Btuin(hft2°F)
W/(m°C)
Btuin(hft2°F)
W/(m°C)
R
W/(m°C)
1/2
(13)
.25
.036
.50
2.84
2.0
.35
1
(25)
.25
.036
.25
1.42
4.2
.74
1-1/2
(38)
.25
.036
.17
0.97
6.0
1.06
2
(51)
.25
.036
.13
0.74
8.0
1.41
The higher the R-Value, the greater the insulating power
Acoustical Performance
Sound Absorption was tested in accordance with ASTM C 423 using a Type A mounting per ASTM E 795.
PRODUCT
ABSORPTION COEFFICIENTS @ OCTAVE BAND FREQUENCIES (Hz)